Tratos has been producing cables for use in the Oil & Gas industry for over 50 years. We provide cables for a large variety of onshore and offshore operations, including umbilical cables for offshore applications, which have been supplied in conjunction with our partner MFX, as well as highly specialised submarine cables.

TRATOS-JBA-MVA-FR-SHF2

Armoured Halogen Free – Fire Resistant- Mud Resistant

Construction

Conductor: tinned copper wire stranded circular class 2

Conductor screen: black semiconductive layer

Insulation: compound type EPR

Insulation screen: black easy strippable semiconductive layer

Screen: plain copper tape

Filler: if necessary

Inner covering: elastomeric compound LSZH

Mica tape

Armour: galvanized steel braid wire*

Outher sheath: elastometric compound SHF2 (MUD resistant)

Standard colour: red

Marking: ELECTRIC CABLE 8700/15000 V + TRATOS A FR SHF2 3×150 EC3N0CMZGZ8C3 IEC 60092-354 IEC 60332-3-22 Cat. A IEC 60331 + lot production + year + metre marking

*Tinned phosphor bronze wire braid (TPBWB) for single core armour if required

Standards

IEC 60092 -354 Single- and three-core power cables with extruded solid insulation for rated voltages 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)

IEC 60092-352 Choice and installation of electric cables

IEC 60092-503 Special features – AC supply systems with voltages in the range of above 1 kV up to and including 15 kV

IEC 60228 conductors of insulated cables

IEC 60092- 360 Insulating and sheathing materials for shipboard and offshore units, power, control, instrumentation and telecommunication cables

IEC 60331 Tests for electric cables under fire conditions – Circuit integrity

IEC 60332-1-2 Test for vertical flame propagation for a single insulated wire or cable

IEC 60332-3-22 Test for vertical flame spread of vertically-mounted bunched wires or cables – Category A

IEC 60754 test on gases evolved during combustion of electric cables

IEC 61034 measurement of smoke density of cables burning under defined conditions

IEC 61892-4 MUD resistance

TRATOS-JBA-MVA-SHF2

MEDIUM VOLTAGE POWER AND CONTROL CABLES BASED ON BS6883 & IEC 60092

Armoured Halogen Free – Mud Resistant

Construction

Conductor: tinned copper wire stranded circular class 2

Conductor screen: black semiconductive layer

Insulation: compound type EPR

Insulation screen: black easy strippable semiconductive layer

Screen: plain copper tape

Filler: if necessary

Inner covering: elastomeric compound LSZH

Armour: Galvanized steel braid wire (GSWB)*

Outher sheath: elastometric compound SHF2 (MUD resistant)

Standard colour: red

Marking: ELECTRIC CABLE 6000/10000 V + TRATOS Cable type (e.g. A SHF2) Cable Size(e.g. “1×150”) COMMODITY CODE IEC 60092-354 IEC 60332-3-22 Cat. A+ lot production + year + metre marking

Standards

IEC 60092 -354 Single- and three-core power cables with extruded solid insulation for rated voltages 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)

IEC 60092-352 Choice and installation of electric cables

IEC 60092-503 Special features – AC supply systems with voltages in the range of above 1 kV up to and including 15 kV

IEC 60228 conductors of insulated cables

IEC 60092- 360 Insulating and sheathing materials for shipboard and offshore units, power, control, instrumentation and telecommunication cables

IEC 60332-1-2 Test for vertical flame propagation for a single insulated wire or cable

IEC 60332-3-22 Test for vertical flame spread of vertically-mounted bunched wires or cables – Category A

IEC 60754 test on gases evolved during combustion of electric cables

IEC 61034 measurement of smoke density of cables burning under defined conditions

IEC 61892-4 MUD resistance

TRATOS-JBA-A-FR-SHF2 - 0,6/1 kV

LOW VOLTAGE POWER AND CONTROL CABLES BASED ON BS6883 & IEC 60092

Armoured Halogen Free – Fire Resistant – Mud Resistant

Construction

Conductor: tinned copper wire stranded circular class 2

Insulation: compound type EPR

Inner covering: elastomeric compound LSZH same comment as above

Mica tape

Armour: Galvanized steel wire braid (GSWB)*

Outher sheath: elastometric compound SHF2 (MUD resistant)

Standard colour: black

Marking: ELECTRIC CABLE 600/1000 V TRATOS Cable type (e.g. A FR SHF2) Cable Size(e.g. “2×2,5+2,5E”) COMMODITY CODE IEC 60332-3-22 Cat. A IEC 60092-353 IEC 60331+ lot production + year + metre marking

*Tinned phosphor bronze wire braid (TPBWB) for single core armour if required

Standards

IEC 60092 – 353 Single and multicore non-radial field power cables with extruded solid insulation for rated voltages 1 kV and 3 kV

IEC 60092-352 Choice and installation of electric cables

IEC 60228 Conductors of insulated cables

IEC 60092- 360 Insulating and sheathing materials for shipboard and offshore units, power, control, instrumentation and telecommunication cables

IEC 60331 Tests for electric cables under fire conditions – Circuit integrity

IEC 60332-1-2 Test for vertical flame propagation for a single insulated wire or cable

IEC 60332-3-22 Test for vertical flame spread of vertically-mounted bunched wires or cables – Category A

IEC 60754 test on gases evolved during combustion of electric cables

IEC 61034 measurement of smoke density of cables burning under defined conditions

IEC 61892-4 MUD resistance

TRATOS-JBA-A-SHF2 - 0,6/1 kV

LOW VOLTAGE POWER AND CONTROL CABLES BASED ON BS6883 & IEC 60092

Armoured Halogen Free – Mud Resistant

Construction

Conductor: tinned copper wire stranded circular class 2 Insulation: compound type EPR

Inner covering: elastomeric compound LSZH here we have a problem, see below

Armour: Galvanized steel wire braid (GSWB)*

Outher sheath: elastomeric compound SHF2 (MUD resistant)

Standard colour: black

Marking: ELECTRIC CABLE 600/1000 V TRATOS Cable type (e.g. A SHF2 MUD) Cable Size(e.g. “2×2,5+2,5E”) COMMODITY CODE IEC 60332-3-22 Cat. A IEC 60092-353 + lot production + year + metre marking

*Tinned phosphor bronze wire braid (TPBWB) for single core armour if required

Standards

IEC 60092 – 353 Single and multicore non-radial field power cables with extruded solid insulation for rated voltages 1 kV and 3 kV

IEC 60092-352 Choice and installation of electric cables

IEC 60228 Conductors of insulated cables

IEC 60092- 360 Insulating and sheathing materials for shipboard and offshore units, power, control, instrumentation and telecommunication cables

IEC 60332-1-2 Test for vertical flame propagation for a single insulated wire or cable

IEC 60332-3-22 Test for vertical flame spread of vertically-mounted bunched wires or cables – Category A

IEC 60754 test on gases evolved during combustion of electric cables

IEC 61034 measurement of smoke density of cables burning under defined conditions

IEC 61892-4 MUD resistance

TRATOS-JBA-U-SHF2

LOW VOLTAGE POWER AND CONTROL CABLES BASED ON BS6883 & IEC 60092-353

Unarmoured Halogen Free – Mud Resistant

Construction

Conductor: tinned copper circular, class 2

Insulation/Outer Sheath: elastomeric compound SHF2 (MUD resistant)

Marking: ELECTRIC CABLE 450/750V + TRATOS-U-SHF2 + Cable Size (e.g. 1×6) COMMODITY CODE IEC 60092-353 IEC 60332-3-22 Cat. A + lot production + year + metre marking

Standards

IEC 60092-353

IEC 60092-352 Choice and installation of electric cables

IEC 60228 Conductors of insulated cables

IEC 60092- 360 Insulating and sheathing materials for shipboard and offshore units, power, control, instrumentation and telecommunication cables

IEC 60332-1-2 Test for vertical flame propagation for a single insulated wire or cable

IEC 60332-3-22 Test for vertical flame spread of vertically-mounted bunched wires or cables – Category A

IEC 60754 test on gases evolved during combustion of electric cables

IEC 61034-2, Measurement of smoke density of cables burning under defined conditions

IEC 61892-4 MUD resistance

Cables

TRATOS-JBA-MVA-FR-SHF2

Armoured Halogen Free - Fire Resistant- Mud Resistant

TRATOS-JBA-MVA-SHF2

Armoured Halogen Free - Mud Resistant

TRATOS-JBA-A-FR-SHF2 - 0,6/1 kV

Armoured Halogen Free - Fire Resistant - Mud Resistant

TRATOS-JBA-A-SHF2 - 0,6/1 kV

Armoured Halogen Free - Mud Resistant

TRATOS-JBA-U-SHF2

Unarmoured Halogen Free - Mud Resistant

TRATOS FIRESAFE-OPTI®

Fibre cables operating in the event of a fire

TRATOS FIRESAFE-SWA/M1®

Firesafe SWA/M1 is designed for fire situations

TRATOS FIRESAFE-TW950e®

Firesafe TW950e is designed for fire situations

TRATOS FIRESAFE-TW950s®

Firesafe TW950s is designed for fire situations

TRATOS FIRESAFE-TW100®

Firesafe TW100 is designed for fire situations