Tratos has been producing cables for use in the oil & gas industry for over 50 years. We provide cables for a large variety of onshore and offshore operations, including umbilical cables for offshore applications, which have been supplied in conjunction with our partner MFX, as well as highly specialised submarine cables.

(XLPE/CuT/TratosCB®/PVC)

POWER cables

(XLPE/CuT/TratosCB®/PVC) – RE4H10H5R4R from 3,6/6 (7,2) kV to 18/30 (36) kV – multi-core – Multi-core, triple extruded insulation, power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present without using Lead.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Fillers: penetrating non hygroscopic compound

Chemical moisture barrier: longitudinally applied Al tape bonded with extruded chemical resistant polymeric layer

Sheath: PVC

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/TratosCB®/PVC)

POWER cables

(XLPE/TratosCB®/PVC) – RE4H5R4R from 3,6/6 (7,2) kV to 18/30 (36) kV – single core – Single core, triple extruded insulation, power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present without using Lead.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Chemical moisture barrier: longitudinally applied Al tape bonded with extruded chemical resistant polymeric layer

Sheath: PVC

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-1 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Test for vertical flame spread, single cable

(XLPE/CuT/Pb/PVC)

POWER cables

(XLPE/CuT/Pb/PVC) – RE4H1HOLR from 3,6/6 (7,2) kV to 18/30 (36) kV – multi-core – Multi-core, triple extruded insulation, lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Fillers: non hygroscopic compound

Metallic sheath: lead alloy

Sheath: PVC

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/Pb/PVC)

POWER cables

(XLPE/Pb/PVC) – RE4LR from 3,6/6 (7,2) kV to 18/30 (36) kV – single core – Single core, triple extruded insulation, lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic sheath: lead alloy

Sheath: PVC

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/CuW/PSA/PE)

POWER cables

(XLPE/CuW/PSA/PE) – RE4H1O(E)E from 3,6/6 (7,2) kV to 18/30 (36) kV – multi-core – Multi-core, triple extruded insulation, non-metallic mechanical protection, sheathed cable for fixed installations for use in Medium Voltage circuits at voltages up to 18/30 (36) kV, in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Fillers: non hygroscopic compound

Mechanical protective layer: PSA AIR BAG™

Sheath: HDPE

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/CuW/PSA/PE)

POWER cables

(XLPE/CuW/PSA/PE) – RE4H1(E)E from 3,6/6 (7,2) kV to 18/30 (36) kV – single core – Single core, triple extruded insulation, non-metallic mechanical protection, sheathed cable for fixed installations for use in Medium Voltage circuits at voltages up to 18/30 (36) kV, in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Fillers: non hygroscopic compound

Mechanical protective layer: PSA AIR BAGTM

Sheath: HDPE

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/CuT/SWA/PVC or XLPE/CuT/SWA/LS0H)

POWER cables

(XLPE/CuT/SWA/PVC or XLPE/CuT/SWA/LS0H) – RE4H1O(M1)RFR(M1) from 3,6/6 (7,2) kV to 18/30 (36) kV – multi-core – Multi-core, triple extruded insulation, armoured and sheathed cable for fixed installations for use in Medium Voltage circuits at voltages up to 18/30 (36) kV, in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Fillers: non hygroscopic compound or LS0H non hygroscopic compound

Separation sheath: PVC or LS0H

Armour: galvanized steel wires

Sheath: PVC or LS0H

Marking:  (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

IEC 60332-3 C Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(XLPE/CuT/AWA/PVC or XLPE/CuT/AWA/LS0H)

POWER cables

(XLPE/CuT/AWA/PVC or XLPE/CuT/AWA/LS0H) – RE4H1R(M1)FR(M1) from 3,6/6 (7,2) kV to 18/30 (36) kV – single core – Single core, triple extruded insulation, non-magnetic armoured, sheathed cable for fixed installations for use in Medium Voltage circuits at voltages up to 18/30 (36) kV, in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Separation sheath: PVC or LS0H

Armour: aluminium wires

Sheath: PVC or LS0H

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

IEC 60332-3 C Fire retardant on bunched cables(if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(XLPE/CuT/PVC or XLPE/CuT/LS0H)

POWER cables

(XLPE/CuT/PVC or XLPE/CuT/LS0H) – RE4H10R(M1) from 3,6/6 (7,2) kV to 18/30 (36) kV – multi-core – Multi-core, triple extruded insulation, sheathed cable for fixed installations for use in Medium Voltage circuits at voltages up to 18/30 (36) kV, in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of IEC 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Fillers: non hygroscopic compound or LS0H non hygroscopic compound

Sheath: PVC or LS0H

Marking:  (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

IEC 60332-3 C Fire retardant on bunched cables(if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(XLPE/CuT/PVC or XLPE/CuT/LS0H)

POWER cables

(XLPE/CuT/PVC or XLPE/CuT/LS0H) – RE4H1R(M1) from 3,6/6 (7,2) kV to 18/30 (36) kV – single core – Single core, triple extruded insulation, sheathed cable for fixed installations for use in Medium Voltage circuits at voltages up to 18/30 (36) kV, in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: are copper circular stranded, according to cl. 2 of IEC 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Sheath: PVC or LS0H

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

IEC 60332-3 C Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(XLPE/SWA/LS0H)

POWER CABLES BASED ON IEC 60502-1

(XLPE/SWA/LS0H) – RTE4OM1FM1 – 0,6/1 kV Armoured fire performance power cable for indoor installations in the petroleum industry, chemical and petrochemical plants. Used where limited circuit integrity in the event of a fire is required.

Construction

Conductor: annealed copper wires according to cl. 2 of BS EN 60228

Fire barrier: mica/glass tape

Insulation: XLPE according to IEC 60502

Identification cores: black numbered

Assembly: concentric layers

Separation sheath: LS0H

Armour: galvanized steel wire

Outer sheath: LS0H

Marking: (ELECTRIC CABLE) + (600/1000 V) + (IEC 60502-1) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502 Design and test guidelines

IEC 60332-1 Test for vertical flame spread, single cable

IEC 60332-3-22 Test for vertical flames spread bunched cables Cat A (if required)

IEC 60331 Tests for electric cables under fire conditions – Circuit integrity

IEC 60754 Determination of acid gas content

IEC 61034 Measurement of smoke density

(XLPE/LS0H)

POWER CABLES BASED ON IEC 60502-1

(XLPE/LS0H) – RTE4OM1 – 0,6/1 kV – Unarmoured fire performance power cable for indoor installations in the petroleum industry, chemical and petrochemical plants. Used where limited circuit integrity in the event of a fire is required.

Construction

Conductor: annealed copper wires according to cl. 2 of BS EN 60228

Fire barrier: mica/glass tape

Insulation: XLPE according to IEC 60502

Identification cores: black numbered

Assembly: concentric layers

Identification cores: black numbered

Assembly: concentric layers

Outer sheath: LS0H

Marking: (ELECTRIC CABLE) + (600/1000 V) + (IEC 60502-1) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502 Design and test guidelines

IEC 60332-1 Test for vertical flame spread, single cable

IEC 60332-3-22 Test for vertical flames spread bunched cables Cat A (if required)

IEC 60331 Tests for electric cables under fire conditions – Circuit integrity

IEC 60754 Determination of acid gas content

IEC 61034 Measurement of smoke density

(XLPE/SWA/PVC or XLPE/SWA/LS0H)

POWER CABLES BASED ON IEC 60502-1

(XLPE/SWA/PVC or XLPE/SWA/LS0H) – RE40RFR(M1) – 0,6/1 kV – Armoured power cable for indoor or outdoor installations in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Insulation: XLPE compound according to IEC 60502

Identification cores: black numbered

Assembly: concentric layers

Fillers: non hygroscopic compound or LS0H non hygroscopic compound

Armour: galvanized steel wire

Sheath: PVC or LS0H

Marking: (ELECTRIC CABLE) + (600/1000 V) + (IEC 60502-1) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502 Design and test guidelines

IEC 60332-1 Test for vertical flame spread, single cable

IEC 60332-3-22 Test for vertical flames spread bunched cables Cat A (if required)

IEC 60754 Determination of acid gas content

IEC 61034 Measurement of smoke density

(XLPE/PVC or XLPE/LS0H)

POWER CABLES BASED ON IEC 60502-1

(XLPE/PVC or XLPE/LS0H) – RE40R(M1) – 0,6/1 kV – Unarmoured power cable for indoor installations in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Insulation: XLPE compound according to IEC 60502

Identification cores: black numbered

Assembly: concentric layers

Penetrant sheath: PVC or LS0H

Marking: (ELECTRIC CABLE) + (600/1000 V) + (IEC 60502-1) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-1 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

IEC 60332-3 C Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties

IEC 61034 Low smoke emission

(XLPE/TratosCB®/PVC)

POWER cables

(XLPE/TratosCB®/PVC) – RE4OH5R4R 0,6/1 kV – multi-core – Multi-core cable for installation in and around process plants where hydrocarbons are present without using Lead.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of IEC 60228

Insulation: XLPE compound

Fillers: non hygroscopic compound

Chemical moisture barrier: longitudinally applied Al tape bonded with extruded chemical resistant polymeric layer

Sheath: PVC

Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)

Standards

IEC 60502-1 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Test for vertical flame spread, single cable

(XLPE/TratosCB®/PVC)

POWER cables

(XLPE/TratosCB®/PVC) – RE4H5R4R 0,6/1 kV – single-core – Single core cable for installation in and around process plants where hydrocarbons are present without using Lead.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of IEC 60228

Insulation: XLPE compound

Chemical moisture barrier: longitudinally applied Al tape bonded with extruded chemical resistant polymeric layer

Sheath: PVC

Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)

Standards

IEC 60502-1 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/Pb/SWA/PVC)

POWER cables

(XLPE/Pb/SWA/PVC) – RE4OLRFR 0,6/1 kV – multi-core – Multi-core, armoured, lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Insulation: XLPE compound according to IEC 60502

Fillers: non hygroscopic compound

Metallic sheath: lead alloy

Separation sheath: PVC

Armour: galvanized steel wires

Sheath: PVC

Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)

Standards

IEC 60502-1 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/Pb/AWA/PVC)

POWER cables

(XLPE/Pb/AWA/PVC) – RE4LRFR 0,6/1 kV – single core – Single core, non-magnetic armoured, lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of IEC 60228

Insulation: XLPE compound according to IEC 60502

Metallic sheath: Lead alloy

Separation sheath: PVC

Armour: aluminium wires

Sheath: PVC

Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)

Standards

IEC 60502-1 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/Pb/PVC)

POWER cables

(XLPE/Pb/PVC) – RE4OLR 0,6/1 kV – multi-core – Multi-core lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Insulation: XLPE compound according to IEC 60502

Fillers: non hygroscopic compound

Metallic sheath: lead alloy

Sheath: PVC

Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)

Standards

IEC 60502-1 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/Pb/PVC)

POWER cables

(XLPE/Pb/PVC) – RE4LR 0,6/1 kV – single core – Single core lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Insulation: XLPE compound according to IEC 60502

Metallic sheath: lead alloy

Sheath: PVC

Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)

Standards

IEC 60502-1 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/SWA/PVC or XLPE/SWA/LS0H)

POWER cables

(XLPE/SWA/PVC or XLPE/SWA/LS0H) – RE4OM1(R)FM1(R) 0,6/1 kV – multi-core – Multi-core armoured and sheathed cable for fixed installations for voltages up to 1000V or up to 750 V d.c. to earth, in the petroleum industry, chemical and petrochemical plants, indoor or outdoor locations.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Insulation: XLPE compound according to IEC 60502

Inner covering: non hygroscopic compound or LS0H non hygroscopic compound

Armour: galvanized steel wire

Sheath: PVC or LS0H

Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)

Standards

IEC 60502-1 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

IEC 60332-3 C Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(XLPE/PVC or XLPE/LS0H)

POWER cables

(XLPE/PVC or XLPE/LS0H) – RE4M1(R) 0,6/1 kV – multi-core – Multi-core sheathed cable for fixed installations for voltages up to 1000V or up to 750 V d.c. to earth, in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Insulation: XLPE compound according to IEC 60502

Fillers: non hygroscopic compound or LS0H non hygroscopic compound

Sheath: PVC or LS0H

Marking: (ELECTRIC CABLE)+(600/1000 V)+ (IEC 60502-1) + (TRATOS) + (batch number)+(number of cores)+(size of conductor) + (Metre mark)

Standards

IEC 60502-1 Design and tests guidelines

BS EN 60228 Conductors

IEC 60332-1 Flame retardant

IEC 60332-3 C Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties

IEC 61034 Low smoke emission

(XLPE/AWA/PVC or XLPE/AWA/LS0H)

POWER cables

(XLPE/AWA/PVC or XLPE/AWA/LS0H) – RE4M1FM1(R) 0,6/1 kV – single core – Single core, non-magnetic, armoured power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of IEC 60228

Insulation: XLPE compound according to IEC 60502

Bedding: non hygroscopic compound or LS0H non hygroscopic compound

Armour: aluminium wires

Sheath: PVC or LS0H

Marking: (ELECTRIC CABLE) + (600/1000 V) + (IEC 60502-1) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-1 Design and tests guidelines

BS EN 60228 Conductors

IEC 60332-1 Flame retardant

IEC 60332-3 C Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(XLPE/PVC or XLPE/LS0H)

POWER cables

(XLPE/PVC or XLPE/LS0H) – RE4M1(R) 0,6/1 kV – single core – Single core sheathed cable for fixed installations for voltages up to 1000V or up to 750 V d.c. to earth, in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Insulation: XLPE compound

Sheath: PVC or LS0H

Marking: (ELECTRIC CABLE) + (600/1000 V) + (IEC 60502-1) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-1 Design and tests guidelines

BS EN 60228 Conductors

IEC 60332-1 Flame retardant

IEC 60332-3 C Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties

IEC 61034 Low smoke emission

(PVC) N07V-K - 0,45/0,75 kV

Earthing cables

Single core unsheathed cable for fixed protected installations for voltages up to 1000V or up to 750 V d.c. to earth, in the petroleum industry, chemical and petrochemical plants. Flexible, fine wire, conductor to aid installation.

Construction

Conductor: bare copper circular flexible, according to cl. 5 of BS EN 60228

Insulation: PVC compound

Marking: (Year of manufacture) + (serial number) + (Tratos cable type) + [(number of cores) × (cross-section)] + (rated voltage)

Standards

CENELEC HD 21 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60227/03 Design and tests guidelines

(PVC/SWA/PVC or XLPE/SWA/LS0H)

CONTROL cables BASED ON EN 50288-7

(PVC/SWA/PVC or XLPE/SWA/LS0H) – RE4HM1FM1(R) – 300/500V – Armoured multi-element metallic control cables for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plants. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.

Construction

Conductor: annealed copper wires according to cl. 2

Insulation: PVC or XLPE

Identification cores: black numbered

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Inner sheath: PVC or LS0H

Armour: galvanized steel wire comply with EN 10244 cl. D

Outer sheath: PVC or LS0H

Marking: (EN 50288-7) + (300/500 V) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

BS EN 60288

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PVC/PVC or XLPE/LS0H)

CONTROL cables BASED ON EN 50288-7

(PVC/PVC or XLPE/LS0H) – RE4OHM1(R) – 300/500V – Unarmoured multi-element metallic control cables for indoor installations in the petroleum industry, chemical and petrochemical plants. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.

Construction

Conductor: annealed copper wires according to cl. 2

Insulation: PVC or XLPE

Identification cores: black numbered

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Outer sheath: PVC or LS0H

Marking: (EN 50288-7) + (300/500 V) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

BS EN 60288

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PVC/SWA/PVC or XLPE/SWA/LS0H)

CONTROL CABLES BASED ON PAS 5308

(PVC/SWA/PVC or XLPE/SWA/LS0H) – (F)(R)OHRFR(M1) – 300/500V – Armoured power cable for indoor or outdoor installations in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: annealed copper wires according to cl. 1 or 2 or 5 of BS EN 60228

Insulation: PVC or XLPE

Identification cores: see table 7 on page 10

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Bedding: PVC or LS0H

Armour: galvanized steel wire

Outer sheath: PVC or LS0H

Marking: (PAS 5308-1) + (300/500 V) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

PAS 5308-1 Design guidelines

IEC 60332-1 Flame retardant

IEC 60332-3C Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PVC/PVC or XLPE/LS0H)

CONTROL cables BASED ON PAS 5308

(PVC/PVC or XLPE/LS0H) – (F)(R)ROHR(M1) – 300/500V – Unarmoured control cable for indoor installations in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: annealed copper wires according to cl. 1 or 2 or 5

Insulation: PVC or XLPE

Identification cores: see table 7 on page 10

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Outer sheath: PVC or LS0H

Marking: (PAS 5308-1) + (300/500 V) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

PAS 5308-1 Design guidelines

IEC 60332-1 Flame retardant

IEC 60332-3C Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PE/SWA/PVC or XLPE/SWA/LS0H)

Thermocouple cables BASED ON EN 50288-7

(PE/SWA/PVC or XLPE/SWA/LS0H) – UE(X)HOHRFR(M1) – 300/500V – Armoured cable for indoor or outdoor installations in the petroleum industry, chemical and petrochemical plants. Used as extension and compensating cable in thermocouple temperature measuring circuits  in and around process plants.

Construction

Conductor: solid alloy

Insulation: polyethylene or XLPE

Pairs: twisted

Identification pairs: according to ANSI MC 96.1 or IEC 60584

Individual screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Outer sheath: PVC or LS0H

Armour: galvanized steel wire

Marking: (EN 50288-7) + (Voltage grade) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PE/PVC or XLPE/LS0H)

Thermocouple cables BASED ON EN 50288-7

(PE/PVC or XLPE/LS0H) – UE(X)HOHR(M1) – 300/500V – Unarmoured cable for indoor installations in the petroleum industry, chemical and petrochemical plants. Used as extension and compensating cable in thermocouple temperature measuring circuits  in and around process plants.

Construction

Conductor: solid alloy

Insulation: polyethylene or XLPE

Pairs: twisted

Identification pairs: according to ANSI MC 96.1 or IEC 60584

Individual screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Outer sheath: PVC or LS0H

Marking: (EN 50288-7) + (Voltage grade) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PE/SWA/PVC or XLPE/SWA/LS0H)

Thermocouple cables BASED ON PAS 5308

(PE/SWA/PVC or XLPE/SWA/LS0H) – METAL – UEXHOHRFR(M1) – 300/500V – Armoured cable for indoor or outdoor installations in the petroleum industry, chemical and petrochemical plants. Used as extension and compensating cable in thermocouple temperature measuring circuits  in and around process plants.

Construction

Conductor: solid alloy conductor

Insulation: polyethene or XLPE

Pairs: twisted

Identification pairs: numbered pairs and colour code according to ANSI MC 96.1 or IEC 60584

Individual screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Bedding: PVC or LSOH

Armour: galvanized steel wire

Outer sheath: PVC or LSOH

Marking: (PAS 5308-1) + (Thermocouple type) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

PAS 5308-1 Design guidelines

IEC 60332-1 Flame retardant

IEC 60332-3C Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PE/PVC or XLPE/LS0H)

Thermocouple cables BASED ON PAS 5308

(PE/PVC or XLPE/LS0H) – METAL – UEXHOHR – 300/500V – Unarmoured cable for indoor installations in the petroleum industry, chemical and petrochemical plants. Used as extension and compensating cable in thermocouple temperature measuring circuits in and around process plants.

Construction

Conductor: solid alloy conductor

Insulation: polyethene or XLPE

Pairs: twisted

Identification pairs: numbered pairs and colour code according to ANSI MC 96.1 or IEC 60584

Individual screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Outer sheath: PVC or LSOH

Marking: (PAS 5308-1) + (Thermocouple type) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

PAS 5308-1 Design guidelines

IEC 60332-1 Flame retardant

IEC 60332-3C Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(SIL/PVC or SIL/LS0H)

Instrumentation cables based on EN 50288-7

(SIL/PVC or SIL/LS0H) – RG4(X)OHM1 – 300V or 500V – Unarmoured silicone rubber insulated multi-element metallic instrumentation cable for indoor installations in the petroleum industry, chemical and petrochemical plants. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.

Construction

Conductor: annealed copper wires according to cl. 2

Insulation: silicon

Triples: twisted

Identification triples: see table 11 & 12 on page 12

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Outer sheath: PVC or LS0H

Marking: (EN 50288-7) + (Voltage grade) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60331 Fire resistant

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(XLPE/LS0H)

Instrumentation cables based on EN 50288-7

(XLPE/LS0H) – RTE4(X)OHM1 – 300V or 500V – Unarmoured fire performance multi-element metallic instrumentation cable for indoor installations in the petroleum industry, chemical and petrochemical plants. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.

Construction

Conductor: annealed copper wires according to cl. 2

Fire barrier: mica/glass tape

Insulation: polyethylene or XLPE

Triples: twisted

Identification triples: see table 11 & 12 on page 12

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Outer sheath: PVC or LS0H

Marking: (EN 50288-7) + (Voltage grade) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PE/PVC or XLPE/PVC or XLPE/LS0H)

Instrumentation cables based on EN 50288-7

(PE/PVC or XLPE/PVC or XLPE/LS0H) – RE4(X)OHR(M1) – 300V or 500V – Unarmoured multi-element metallic instrumentation cables for indoor use in analogue and digital communication and control. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.

Construction

Conductor: annealed copper wires according to cl. 2

Insulation: polyethylene or XLPE

Triples: twisted

Identification triples: see table 11 & 12 on page 12

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Outer sheath: PVC or LS0H

Marking: (EN 50288-7) + (Voltage grade) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(SIL/SWA/PVC or SIL/SWA/LS0H)

Instrumentation cables based on EN 50288-7

(SIL/SWA/PVC or SIL/SWA/LS0H) – RG4(X)OHM1FM1 – 300V or 500V – Armoured silicone rubber insulated multi-element metallic instrumentation cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plants. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.

Construction

Conductor: annealed copper wires according to cl. 2

Insulation: silicon

Pairs: twisted

Identification pairs: see table 11 & 12 on page 12

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Inner sheath: PVC or LS0H

Armour: galvanized steel wire

Outer sheath: PVC or LS0H

Marking: (EN 50288-7) + (Voltage grade) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60331 Fire resistant

IEC 60754 Halogen free properties

IEC 61034 Low smoke emission

(XLPE/SWA/LS0H)

Instrumentation cables based on EN 50288-7

(XLPE/SWA/LS0H) – RTE4(X)OHM1FM1 – 300V or 500V – Armoured fire performance multi-element metallic instrumentation cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plants. Used where limited circuit integrity in the event of a fire is required. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.

Construction

Conductor: annealed copper wires according to cl. 2

Fire barrier: mica/glass tape

Insulation: polyethylene or XLPE

Pairs: twisted

Identification see table 11 & 12 on page 12

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Armour: galvanized steel wire

Outer sheath: PVC or LS0H

Marking: (EN 50288-7) + (Voltage grade) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60331 Fire resistant

IEC 60754 Halogen free properties

IEC 61034 Low smoke emission

(SIL/PVC or SIL/LS0H)

Instrumentation cables based on EN 50288-7

(SIL/PVC or SIL/LS0H) – RG4(X)OHM1 – 300V or 500V – Unarmoured silicone rubber insulated multi-element metallic instrumentation cable for indoor installations in the petroleum industry, chemical and petrochemical plants. Used for control and instrumentation as well as for data & voice transmission. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.

Construction

Conductor: annealed copper wires according to cl. 2

Insulation: silicone

Pairs: twisted

Identification pairs: see table 11 & 12 on page 12

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Outer sheath: PVC or LS0H

Marking: (EN 50288-7) + (Voltage grade) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60331 Fire resistant

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(XLPE/LS0H)

Instrumentation cables based on EN 50288-7

(XLPE/LS0H) – RTE4(X)OHM1 – 300V or 500V – Unarmoured fire performance multi-element metallic instrumentation cable for indoor installations in the petroleum industry, chemical and petrochemical plants. Used for control and instrumentation as well as for data & voice transmission. Used where limited circuit integrity in the event of a fire is required. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.

Construction

Conductor: annealed copper wires according to cl. 2

Fire barrier: mica/glass tape

Insulation: polyethylene or XLPE

Pairs: twisted

Identification pairs: see table 11 & 12 on page 12

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Outer sheath: PVC or LS0H
Marking: (EN 50288-7) + (Voltage grade) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60331 Fire resistant

IEC 60754 Halogen free properties

IEC 61034 Low smoke emission

(PE/TratosCB®/SWA/PVC or XLPE/TratosCB®/SWA/PVC or XLPE/TratosCB®/SWA/LS0H)

Instrumentation cables based on EN 50288-7

(PE/TratosCB®/SWA/PVC or XLPE/TratosCB®/SWA/PVC or XLPE/TratosCB®/SWA/LS0H)  RE4(X)OHRH5R4FR(M1) – 300V or 500V – Armoured multi-element metallic instrumentation cables for indoor or outdoor use in analogue and digital communication and control in and around process plants where hydrocarbons are present without using Lead. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.

Construction

Conductor: annealed copper wires according to cl. 2

Insulation: polyethylene or XLPE

Pairs: twisted

Identification pairs: see table 11 & 12 on page 12

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Chemical moisture barrier: longitudinally applied AI tape bonded with extruded chemical resistant polymeric layer

Armour: galvanized steel wire

Outer sheath: PVC or LS0H

Marking: (EN 50288-7) + (Voltage grade) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PE/Pb/SWA/PVC or XLPE/Pb/SWA/PVC or XLPE/Pb/SWA/LS0H)

Instrumentation cables based on EN 50288-7

(PE/Pb/SWA/PVC or XLPE/Pb/SWA/PVC or XLPE/Pb/SWA/LS0H) – RE4(X)OHRLRFR(M1) – 300V or 500V – Armoured multi-element metallic instrumentation cables for indoor or outdoor use in analogue and digital communication and control in and around process plants where hydrocarbons are present. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.

Construction

Conductor: annealed copper wires according to cl. 2

Insulation: polyethene or XLPE

Pairs: twisted

Identification pairs: see table 11 & 12 on page 12

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Bedding: PVC or LSOH

Lead sheath

Inner sheath: PVC or LSOH

Armour: galvanized steel wire

Outer sheath: PVC or LSOH

Marking: (EN 50288-7) + (Voltage grade) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PE/SWA/PVC or XLPE/SWA/LS0H or XLPE/SWA/PVC)

Instrumentation cables based on EN 50288-7

(PE/SWA/PVC or XLPE/SWA/LS0H or XLPE/SWA/PVC) – RE4(X)HOHR(M1)FR(M1) – 300V or 500V – Armoured multi-element metallic instrumentation cables for indoor or outdoor use in analogue and digital communication and control where higher levels of screening than provided by collective screen is required. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.

Construction

Conductor: annealed copper wires according to cl. 2

Insulation: polyethylene or XLPE

Pairs: twisted

Identification pairs: see table 11 & 12 on page 12

Individual screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Inner sheath: PVC or LS0H

Armour: galvanized steel wire

Outer sheath: PVC or LS0H

Marking: (EN 50288-7) + (Voltage grade) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PE/SWA/PVC or XLPE/SWA/LS0H or XLPE/SWA/PVC)

Instrumentation cables based on EN 50288-7

(PE/SWA/PVC or XLPE/SWA/LS0H or XLPE/SWA/PVC) – RE4(X)OHR(M4)FR(M1) – 300V or 500 V – Armoured multi-element metallic instrumentation cables for indoor or outdoor use in analogue and digital communication and control. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.

Construction

Conductor: annealed copper wires according to cl. 2

Insulation: polyethene or XLPE

Pairs: twisted

Identification pairs: see table 11 & 12 on page 12

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Inner sheath: PVC or LSOH

Armour: galvanized steel wire

Outer sheath: PVC or LS0H

Marking: (EN 50288-7) + (Voltage grade) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PE/PVC or XLPE/PVC or XLPE/LS0H)

Instrumentation cables based on EN 50288-7

(PE/PVC or XLPE/PVC or XLPE/LS0H) – RE4(X)HOHR(M1) – 300V or 500V – Unarmoured multi-element metallic instrumentation cables for indoor use in analogue and digital communication and control in and around process plants where higher levels of screening than provided by collective screen is required. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.

Construction

Conductor: annealed copper wires according to cl. 2

Insulation: polyethene or XLPE

Pairs: twisted

Identification pairs: see table 11 & 12 on page 12

Individual screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Outer sheath: PVC or LSOH

Marking: (EN 50288-7) + (Voltage grade) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PE/PVC or XLPE/PVC or XLPE/LS0H)

Instrumentation cables based on EN 50288-7

(PE/PVC or XLPE/PVC or XLPE/LS0H) – RE4(X)OHR(M1) – 300V or 500 V – Unarmoured multi-element metallic instrumentation cables for indoor use in analogue and digital communication and control. Important Note: These cables are not intended for direct connection to mains electricity supply or other low impedance sources.

Construction

Conductor: annealed copper wires according to cl. 2

Insulation: polyethene or XLPE

Pairs: twisted

Identification pairs: see table 11 & 12 on page 12

Assembly: concentric layers

Overall screen: aluminium/polyester tape 0.024 mm in electrical contact with tinned annealed copper wires of a total section of 0.5mm2 polyester tape 0.023 mm

Outer sheath: PVC or LSOH

Marking: (EN 50288-7) + (Voltage grade) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

EN 50288-7 Design guidelines

EN 50290-2 Specification for insulation and sheath material

IEC 60332-1 Flame retardant

IEC 60332-3A Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(XLPE/SWA/LS0H) Collective screen

Instrumentation cables based on PAS 5308

(XLPE/SWA/LS0H) – (F)(U)(R)TE4XOHM1FM1 – 300/500 V – Based on Part 1 Type 2 Collective screen. Armoured for indoor or outdoor installations generally within the harsh demanding environment encountered in the petroleum industry, chemical and petrochemical plants. Used for control and instrumentation as well as for data & voice transmission. Also used for the interconnection of electrical equipment and instruments, particularly in and around process plants. Used where limited circuit integrity in the event of a fire is required.

Construction

Conductor: Plain annealed copper wire conductors to BS EN 60228 cl.1, cl.2 or cl.5

Fire barrier – mica-glass tape

Insulation: XLPE

Cores twisted into pairs

Cabling of pairs: in concentric layers

Tape: Polyester binder tape

Collective screen: Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire

Bedding: LSOH to BS EN 50290-2-27

Armour: Single layer galvanised steel wire armour to BS EN 10257-1

Outer sheath: LSOH

Marking: (PAS 5308-2) + (300/500 V) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

Based on PAS 5308-1 Design guideline

IEC 60332-1 Flame retardant

IEC 60332-3C Fire retardant on bunched cables (if required)

IEC 60331 Circuit integrity test

IEC 60754 Halogen free properties

IEC 61034 Low smoke emission

(XLPE/LS0H) Collective screen

Instrumentation cables based on PAS 5308

(XLPE/LS0H) – (F)(U)(R)TE4X(O)HM1 – 300/500 V – Based on Part 1 Type 1 Collective screen. Unarmoured fire performance cable for indoor installations in the petroleum industry, chemical and petrochemical plants. Used for control and instrumentation as well as for data & voice transmission. Also used for the interconnection of electrical equipment and instruments, particularly in and around process plants. Used where limited circuit integrity in the event of a fire is required.

Construction

Conductor: Plain annealed copper wire conductors to BS EN 60228 cl.1, cl.2 or cl.5

Fire barrier: Mica-glass tape

Insulation: XLPE

Cores twisted into pairs

Cabling of pairs: in concentric layers

Tape: Polyester binder tape

Collective screen: Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire

Outer sheath: LSOH

Marking: (PAS 5308-1) + (300/500 V) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

Based PAS 5308-1 Design guideline

IEC 60332-1 Flame retardant

IEC 60332-3C Fire retardant on bunched cables (if required)

IEC 60331 Circuit integrity test

IEC 60754 Halogen free properties

IEC 61034 Low smoke emission

(PVC/SWA/PVC) Individual and collective screen

Instrumentation cables based on PAS 5308

(PVC/SWA/PVC) – (F)(R)RXHOHRFR – 300/500 V – Part 2 Type 2 Individual and collective screen. Armoured for indoor or outdoor installations generally within the harsh demanding environment encountered in the petroleum industry, chemical and petrochemical plants. Used for control and instrumentation as well as for data & voice transmission in process plants.

Construction

Conductor: Plain annealed copper wire conductors to BS EN 60228 cl.1, cl.2 or cl.5

Insulation: PVC

Cores twisted into pairs

Individual pair screen:
a) Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire
b) Polyester isolating tape(s) numbered for identification

Cabling of pairs: in concentric layers

Tape: Polyester binder tape

Collective screen: Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire

Bedding: PVC

Armour: Single layer galvanised steel wire armour to BS EN 10257-1

Outer sheath: PVC

Marking: (PAS 5308-2) + (300/500 V) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

PAS 5308-2 Design guidelines

IEC 60332-1 Flame retardant

IEC 60332-3 Flame retardant bunched cables (if required)

(PVC/SWA/PVC) Collective screen

Instrumentation cables based on PAS 5308

(PVC/SWA/PVC) – (F)(R)RXOHRFR – 300/500 V – Part 2 Type 2 Collective screen. Armoured for indoor or outdoor installations generally within the harsh demanding environment encountered in the petroleum industry, chemical and petrochemical plants. Used for control and instrumentation as well as for data & voice transmission. Also used for the interconnection of electrical equipment and instruments, particularly in and around process plants.

Construction

Conductor: Plain annealed copper wire conductors to BS EN 60228 cl.1, cl.2 or cl.5

Insulation: PVC

Cores twisted into pairs

Cabling of pairs: in concentric layers

Tape: Polyester binder tape

Collective screen: Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire

Bedding: PVC

Armour: Single layer galvanised steel wire armour to BS EN 10257-1

Outer sheath: PVC

Marking: (PAS 5308-2) + (300/500 V) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

PAS 5308-2 Design guidelines

IEC 60332-1 Flame retardant

IEC 60332-3 Flame retardant bunched cables (if required)

(PVC/PVC) Individual and collective screen

Instrumentation cables based on PAS 5308

(PVC/PVC) – (F)(R)RXHOHR – 300/500 V – Part 2 Type 1 Individual and collective screen. Unarmoured for indoor installations in the petroleum industry, chemical and petrochemical plants. Used for control and instrumentation as well as for data & voice transmission. Also used for the interconnection of electrical equipment and instruments, particularly in and around process plants.

Construction

Conductor: Plain annealed copper wire conductors to BS EN 60228 cl.1, cl.2 or cl.5

Insulation: PVC

Cores twisted into pairs

Individual pair screen
a) Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire
b) Polyester isolating tape(s) numbered for identification

Cabling of pairs: in concentric layers

Tape: Polyester binder tape

Collective screen: Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire

Outer sheath: PVC

Marking: (PAS 5308-2) + (300/500 V) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

PAS 5308-2 Design guidelines

IEC 60332-1 Flame retardant

IEC 60332-3 Flame retardant bunched cables (if required)

(PVC/PVC) Collective screen

Instrumentation cables based on PAS 5308

(PVC/PVC) – (F)(U)(R)RX(O)HR – 300/500 V – Part 2 Type 1 Collective screen. Unarmoured for indoor installations in the petroleum industry, chemical and petrochemical plants. Used for control and instrumentation as well as for data & voice transmission. Also used for the interconnection of electrical equipment and instruments, particularly in and around process plants.

Construction

Conductor: Plain annealed copper wire conductors to BS EN 60228 cl.1, cl.2 or cl.5

Insulation: PVC

Cores twisted into pairs

Cabling of pairs: in concentric layers

Tape: Polyester binder tape

Collective screen: Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire

Outer sheath: PVC

Marking: (PAS 5308-2) + (300/500 V) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

PAS 5308-2 Design guidelines

IEC 60332-1 Flame retardant

IEC 60332-3 Flame retardant bunched cables (if required)

(PE/AL-TAPE/SWA/PVC or XLPE/Tratos CB®/SWA/LS0H)

Instrumentation cables based on PAS 5308

(PE/AL-TAPE/SWA/PVC or XLPE/Tratos CB®/SWA/LS0H) – REXOHRH5R4FR – 300/500 V – Part 1 Type 2 Collective screen or Part 1 Type 3 Collective screen. Armoured for indoor or outdoor installations generally within the harsh demanding environment encountered in the petroleum industry, chemical and petrochemical plants. Used for control and instrumentation as well as for data & voice transmission. Also used for the interconnection of electrical equipment and instruments, particularly in and around process plants where hydrocarbons are present or a moisture barrier is required.

Construction

Conductor: Plain annealed copper wire conductors to BS EN 60228 cl.1, cl.2 or cl.5

Insulation: polyethene or XLPE

Cores twisted into pairs

Cabling of pairs: in concentric layers

Tape: Polyester binder tape

Collective screen: Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire

Bedding: polyethylene or LSOH

Chemical/moisture barrier:  longitudinal overlapped aluminium metallic foil may be used which is bonded to the inner surface of an extruded plastic sheath.

Armour: Single layer galvanised steel wire armour to BS EN 10257-1

Outer sheath: PVC or LSOH

Marking: (PAS 5308-1) + (300/500 V) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

PAS 5308-1 Design guidelines

IEC 60332-1 Flame retardant

IEC 60332-3 Flame retardant bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PE/Pb/SWA/PVC or XLPE/Pb/SWA/LS0H)

Instrumentation cables based on PAS 5308

(PE/Pb/SWA/PVC or XLPE/Pb/SWA/LS0H) – (F)(R)(U)EXHRLRFR(M1) – 300/500 V – Part 1 Type 3 Collective screen. Armoured for indoor or outdoor installations generally within the harsh demanding environment encountered in the petroleum industry, chemical and petrochemical plants. Used for control and instrumentation as well as for data & voice transmission. Also used for the interconnection of electrical equipment and instruments, particularly in and around process plants where hydrocarbons are present.

Construction

Conductor: Plain annealed copper wire conductors to BS EN 60228 cl.1, cl.2 or cl.5

Insulation: polyethene or XLPE

Cores twisted into pairs

Cabling of pairs: in concentric layers

Tape: Polyester binder tape

Collective screen: Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire

Bedding: Type LD black polyethylene to BS EN 50290-2-24 or LSOH to BS EN 50290-2-27

Chemical barrier: Lead sheath

Bedding: Type LD black polyethylene to BS EN 50290-2-24 or LSOH to BS EN 50290-2-27

Armour: Single layer galvanised steel wire armour to BS EN 10257-1

Outer sheath: PVC or LSOH

Marking: (PAS 5308-1) + (300/500 V) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

PAS 5308-1 Design guidelines

IEC 60332-1 Flame retardant

IEC 60332-3 Flame retardant bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PE/SWA/PVC or XLPE/SWA/LS0H) - Individual screen

Instrumentation cables based on PAS 5308

(PE/SWA/PVC or XLPE/SWA/LS0H) – (F)(R)(U)EXHOHEFR(M1) – 300/500 V – Part 1 Type 2 Individual screen. Armoured for indoor or outdoor installations generally within the harsh demanding environment encountered in the petroleum industry, chemical and petrochemical plants. Used for control and instrumentation as well as for data & voice transmission. Also used for the interconnection of electrical equipment and instruments, particularly in and around process plants where higher levels of screening than provided by collective screen is required.

Construction

Conductor: Plain annealed copper wire conductors to BS EN 60228 cl.1, cl.2 or cl.5

Insulation: polyethene or XLPE

Individual pair screen:
a)
Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire
b) Polyester isolating tape(s) numbered for identification

Cabling of pairs: in concentric layers

Tape: Polyester binder tape

Collective screen: Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire

Bedding: Type LD black polyethylene to BS EN 50290-2-24 or LSOH to BS EN 50290-2-27

Armour: Single layer galvanised steel wire armour to BS EN 10257-1

Outer sheath: PVC or LSOH

Marking: (PAS 5308-1) + (300/500 V) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

PAS 5308-1 Design guidelines

IEC 60332-1 Flame retardant

IEC 60332-3 Flame retardant bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PE/SWA/PVC or XLPE/SWA/LS0H) - Collective screen

Instrumentation cables based on PAS 5308

(PE/SWA/PVC or XLPE/SWA/LS0H) – (F)(R)(U)EXHEFR(M1) – 300/500 V – Part 1 Type 2 Collective screen. Armoured for indoor or outdoor installations generally within the harsh demanding environment encountered in the petroleum industry, chemical and petrochemical plants. Used for control and instrumentation as well as for data & voice transmission. Also used for the interconnection of electrical equipment and instruments, particularly in and around process plants.

Construction

Conductor: Plain annealed copper wire conductors to BS EN 60228 cl.1, cl.2 or cl.5

Insulation: polyethene or XLPE

Cores twisted into pairs

Cabling of pairs: in concentric layers

Tape: Polyester binder tape

Collective screen: Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire

Bedding: PE Bedding in accordance with BS EN 50290-2-24 or PVC TM51 bedding in accordance with BS EN 50290-2-22

Armour: Single layer galvanised steel wire armour to BS EN 10257-1

Outer sheath: PVC or LSOH

Marking: (PAS 5308-1) + (300/500 V) + (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

PAS 5308-1 Design guidelines

IEC 60332-1 Flame retardant

IEC 60332-3 Flame retardant bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PE/PVC or XLPE/LS0H) - Individual screen

Instrumentation cables based on PAS 5308

(PE/PVC or XLPE/LS0H) – (F)(R)(U)EXHOHR(M1) – 300/500 V – Part 1 Type 1 Individual screen. Unarmoured for indoor installations in the petroleum industry, chemical and petrochemical plants. Used for control and instrumentation as well as for data & voice transmission. Also used for the interconnection of electrical equipment and instruments, particularly in and around process plants where higher levels of screening than provided by collective screen is required.

Construction

Conductor: Plain annealed copper wire conductors to BS EN 60228 cl.1, cl.2 or cl.5

Insulation: polyethene or XLPE

Individual pair screen
a) Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire
b) Polyester isolating tape(s) numbered for identification

Cabling of pairs: in concentric layers

Tape: Polyester binder tape

Collective screen: Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire

Outer sheath: PVC or LSOH

Marking: (PAS 5308-1) + (300/500 V) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

PAS 5308-1 Design guidelines

IEC 60332-1 Flame retardant

IEC 60332-3 Flame retardant bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(PE/PVC or XLPE/LS0H) - Collective screen

Instrumentation cables based on PAS 5308

(PE/PVC or XLPE/LS0H) – (F)(R)(U)E(X)OHR(M1) – 300/500 V – Part 1 Type 1 Collective screen. Unarmoured for indoor installations in the petroleum industry, chemical and petrochemical plants. Used for control and instrumentation as well as for data & voice transmission. Also used for the interconnection of electrical equipment and instruments, particularly in and around process plants.

Construction

Conductor: Plain annealed copper wire conductors to BS EN 60228 cl.1, cl.2 or cl.5

Insulation: polyethene or XLPE

Cores twisted into pairs

Cabling of pairs: in concentric layers

Tape: Polyester binder tape

Collective screen: Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire

Outer sheath: PVC or LSOH

Marking: (PAS 5308-1) + (300/500 V) +  (TRATOS) + (Year of Manufacture) + (Batch Number) + (Metre Mark)

Standards

PAS 5308-1 Design guidelines

IEC 60332-1 Flame retardant

IEC 60332-3 Flame retardant bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

Cables

(XLPE/CuT/TratosCB®/PVC)

Multi-core, triple extruded insulation, power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present without using Lead

(XLPE/TratosCB®/PVC)

Single core, triple extruded insulation, power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present without using Lead

(XLPE/CuT/Pb/PVC)

Multi-core, triple extruded insulation, lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present

(XLPE/Pb/PVC)

Single core, triple extruded insulation, lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present

(XLPE/CuW/PSA/PE)

Multi-core, triple extruded insulation, non-metallic mechanical protection, sheathed cable for fixed installations for use in Medium Voltage circuits at voltages up to 18/30 (36) kV, in the petroleum industry, chemical and petrochemical plants

(XLPE/CuW/PSA/PE)

Single core, triple extruded insulation, non-metallic mechanical protection, sheathed cable for fixed installations for use in Medium Voltage circuits at voltages up to 18/30 (36) kV, in the petroleum industry, chemical and petrochemical plants

TRATOS® BFOU(c) S4/S8

CU/MT/EPR/ZERO HAL/TCWB/EVA - Halogen Free, MUD Resistant & Fire Resistant - Common Screen

TRATOS® BFOU(i) S3/S7

CU/MT/EPR/ZERO HAL/TCWB/EVA - Halogen Free, MUD Resistant & Fire Resistant - Individual Screen

TRATOS® BFOU P5/P12

CU/MT/EPR/ZERO HAL/TCWB/EVA - Halogen Free, MUD Resistant & Fire Resistant

TRATOS® UX P15

CU/EVA - Halogen Free & MUD Resistant

TRATOS® RFOU P4/P11 - 8.7/15 kV - TRATOS® RFOU P19/P21 - 12/20 kV

CU/EPR/ZERO HAL/TCWB/EVA - Halogen Free & MUD Resistant

TRATOS® RFOU P2/P9 - 3.6/6 kV - TRATOS® RFOU P3/P10 - 6/10 kV

CU/EPR/ZERO HAL/TCWB/EVA - Halogen Free & MUD Resistant

TRATOS-JBA-MVA-FR-SHF2

Armoured Halogen Free - Fire Resistant- Mud Resistant

TRATOS-JBA-MVA-SHF2

Armoured Halogen Free - Mud Resistant

TRATOS-JBA-A-FR-SHF2 - 0,6/1 kV

Armoured Halogen Free - Fire Resistant - Mud Resistant

TRATOS-JBA-A-SHF2 - 0,6/1 kV

Armoured Halogen Free - Mud Resistant

TRATOS-JBA-U-SHF2

Unarmoured Halogen Free - Mud Resistant

TRATOS-ACS-FR-SW2-F0 - TRATOS-ACS-FR-SW4-F0

TRATOS-ACS-FR-SW2-F0 (or F1) - Armoured Collectively Screened Reduced Halogen Fire Resistant, TRATOS-ACS-FR-SW4-F0 (or F1) - Armoured Collectively Screened Halogen Free

TRATOS-AIS-FR-SW2-F0 - TRATOS-AIS-FR-SW4-F0

TRATOS-AIS-FR-SW2-F0 (or F1) - Armoured Individually Screened Reduced Halogen Fire Resistant, TRATOS-AIS-FR-SW4-F0 (or F1) - Armoured Individually Screened Halogen Free Fire Resistant

TRATOS-ACS-SW2 - TRATOS-ACS-SW4

TRATOS-ACS-SW2 - Armoured Collectively Screened Reduced Halogen, TRATOS-ACS-SW4 - Armoured Collectively Screened Halogen Free

TRATOS-AIS-SW2 - TRATOS-AIS-SW4

TRATOS-AIS-SW2 - Armoured Individually Screened Reduced Halogen, TRATOS-AIS-SW4 - Armoured Individually Screened Halogen Free

TRATOS-UCS-SW2 - TRATOS-UCS-SW4

TRATOS-UCS-SW2 - Unarmoured Collectively Screened Reduced Halogen, TRATOS-UCS-SW4 - Unarmoured Collectively Screened Halogen Free

TRATOS-UIS-SW2 - TRATOS-UIS-SW4

TRATOS-UIS-SW2 - Unarmoured Individually Screened Reduced Halogen, TRATOS-UIS-SW4 - Unarmoured Individually Screened Halogen Free