Across international transport infrastructure, marine, power generation and transmission industries, Tratos’ Medium Voltage (MV) cables are built for the harshest environmental challenges.

TratoSubmarine® - Power

MEDIUM VOLTAGE CABLES

CU2, HEPR,CTS, PE, Double steel armouring, PE 3KV, 6KV, 10KV, 15KV, 20KV, 30KV, 45 KV. Single core cable or three core cables. Three cores armoured cables.

Construction

Where to use them: utilities, suitable for power transmission.

1 Copper or aluminium circular stranded conductor (filled if required)
2 Extruded semi-conducting layer
3 HEPR insulation
4 Extruded semi-conducting layer
5 Copper tapes screen (as standards require)
6 Non hygroscopic filler
7 Special hygroscopic Pe innersheath
8 Double  Galvanised steel wire armour
9 Special Hygroscopic PE oversheath
10 Marking

Standards

According to  IEC 60228 AND IEC 60502-2,  IEC 60840 to 26/45 kV

(XLPE/CuT/TratosCB®/PVC)

POWER cables

(XLPE/CuT/TratosCB®/PVC) – RE4H10H5R4R from 3,6/6 (7,2) kV to 18/30 (36) kV – multi-core – Multi-core, triple extruded insulation, power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present without using Lead.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Fillers: penetrating non hygroscopic compound

Chemical moisture barrier: longitudinally applied Al tape bonded with extruded chemical resistant polymeric layer

Sheath: PVC

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/TratosCB®/PVC)

POWER cables

(XLPE/TratosCB®/PVC) – RE4H5R4R from 3,6/6 (7,2) kV to 18/30 (36) kV – single core – Single core, triple extruded insulation, power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present without using Lead.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Chemical moisture barrier: longitudinally applied Al tape bonded with extruded chemical resistant polymeric layer

Sheath: PVC

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/CuT/Pb/PVC)

POWER cables

(XLPE/CuT/Pb/PVC) – RE4H1HOLR from 3,6/6 (7,2) kV to 18/30 (36) kV – multi-core – Multi-core, triple extruded insulation, lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Fillers: non hygroscopic compound

Metallic sheath: lead alloy

Sheath: PVC

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/Pb/PVC)

POWER cables

(XLPE/Pb/PVC) – RE4LR from 3,6/6 (7,2) kV to 18/30 (36) kV – single core – Single core, triple extruded insulation, lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic sheath: lead alloy

Sheath: PVC

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/CuW/PSA/PE)

POWER cables

(XLPE/CuW/PSA/PE) – RE4H1O(E)E from 3,6/6 (7,2) kV to 18/30 (36) kV – multi-core – Multi-core, triple extruded insulation, non-metallic mechanical protection, sheathed cable for fixed installations for use in Medium Voltage circuits at voltages up to 18/30 (36) kV, in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Fillers: non hygroscopic compound

Mechanical protective layer: PSA AIR BAG™

Sheath: HDPE

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/CuW/PSA/PE)

POWER cables

(XLPE/CuW/PSA/PE) – RE4H1(E)E from 3,6/6 (7,2) kV to 18/30 (36) kV – single core – Single core, triple extruded insulation, non-metallic mechanical protection, sheathed cable for fixed installations for use in Medium Voltage circuits at voltages up to 18/30 (36) kV, in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Fillers: non hygroscopic compound

Mechanical protective layer: PSA AIR BAGTM

Sheath: HDPE

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

(XLPE/CuT/SWA/PVC or XLPE/CuT/SWA/LS0H)

POWER cables

(XLPE/CuT/SWA/PVC or XLPE/CuT/SWA/LS0H) – RE4H1O(M1)RFR(M1) from 3,6/6 (7,2) kV to 18/30 (36) kV – multi-core – Multi-core, triple extruded insulation, armoured and sheathed cable for fixed installations for use in Medium Voltage circuits at voltages up to 18/30 (36) kV, in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Fillers: non hygroscopic compound or LS0H non hygroscopic compound

Separation sheath: PVC or LS0H

Armour: galvanized steel wires

Sheath: PVC or LS0H

Marking:  (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

IEC 60332-3 C Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(XLPE/CuT/AWA/PVC or XLPE/CuT/AWA/LS0H)

POWER cables

(XLPE/CuT/AWA/PVC or XLPE/CuT/AWA/LS0H) – RE4H1R(M1)FR(M1) from 3,6/6 (7,2) kV to 18/30 (36) kV – single core – Single core, triple extruded insulation, non-magnetic armoured, sheathed cable for fixed installations for use in Medium Voltage circuits at voltages up to 18/30 (36) kV, in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of BS EN 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Separation sheath: PVC or LS0H

Armour: aluminium wires

Sheath: PVC or LS0H

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

IEC 60332-3 C Fire retardant on bunched cables(if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(XLPE/CuT/PVC or XLPE/CuT/LS0H)

POWER cables

(XLPE/CuT/PVC or XLPE/CuT/LS0H) – RE4H10R(M1) from 3,6/6 (7,2) kV to 18/30 (36) kV – multi-core – Multi-core, triple extruded insulation, sheathed cable for fixed installations for use in Medium Voltage circuits at voltages up to 18/30 (36) kV, in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: bare copper circular stranded, according to cl. 2 of IEC 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Fillers: non hygroscopic compound or LS0H non hygroscopic compound

Sheath: PVC or LS0H

Marking:  (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

IEC 60332-3 C Fire retardant on bunched cables(if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

(XLPE/CuT/PVC or XLPE/CuT/LS0H)

POWER cables

(XLPE/CuT/PVC or XLPE/CuT/LS0H) – RE4H1R(M1) from 3,6/6 (7,2) kV to 18/30 (36) kV – single core – Single core, triple extruded insulation, sheathed cable for fixed installations for use in Medium Voltage circuits at voltages up to 18/30 (36) kV, in the petroleum industry, chemical and petrochemical plants.

Construction

Conductor: are copper circular stranded, according to cl. 2 of IEC 60228

Semiconducting layer: extruded compound

Insulation: XLPE compound according to IEC 60502

Semiconducting layer: extruded compound

Metallic screen: copper tapes

Sheath: PVC or LS0H

Marking: (ELECTRIC CABLE) + (Voltage Rating) + (IEC 60502-2) + (TRATOS) + (batch number) + (number of cores) + (size of conductor) + (Metre mark)

Standards

IEC 60502-2 Design and tests guidelines

IEC 60228 Conductors

IEC 60332-1 Flame retardant

IEC 60332-3 C Fire retardant on bunched cables (if required)

IEC 60754 Halogen free properties (only for LS0H)

IEC 61034 Low smoke emission (only for LS0H)

Cables

TratoSubmarine® - Power

Single core cable or three core cables. Three cores armoured cables.

(XLPE/CuT/TratosCB®/PVC)

Multi-core, triple extruded insulation, power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present without using Lead

(XLPE/TratosCB®/PVC)

Single core, triple extruded insulation, power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present without using Lead

(XLPE/CuT/Pb/PVC)

Multi-core, triple extruded insulation, lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present

(XLPE/Pb/PVC)

Single core, triple extruded insulation, lead sheathed power cable for indoor and outdoor installations in the petroleum industry, chemical and petrochemical plant in and around process plants where hydrocarbons are present

(XLPE/CuW/PSA/PE)

Multi-core, triple extruded insulation, non-metallic mechanical protection, sheathed cable for fixed installations for use in Medium Voltage circuits at voltages up to 18/30 (36) kV, in the petroleum industry, chemical and petrochemical plants