TRATOS® PAS 5308 Part 1/Type 1 – Unarmoured Construction

Control and Instrumentation cable

Energy Cables / Low Voltage Cables - LV / LV Energy Cables BS

TRATOS® PAS 5308 Part 1/Type 1 – Unarmoured Construction

Publicly Available Specification PAS 5308-1 replaces BS 5308-1 and provides additional aspects not covered in the European standard for control and instrumentation cables, BS EN 50288-7. As the actual manufacturer of these cables, not simply a distributor, Tratos has total control of the design, quality and manufacturing process from the purchase of the raw materials through to final testing and despatch to our customers. Having control of the manufacturing process Tratos can ensure compatibility with most makes and types of glands. Tratos manufacture a complete range of control and instrumentation cables for industrial applications. Tratos control and instrumentation cables are available with either Class 1, Class 2 or, to aid installation and allow repeated removal of meters for calibration, Class 5 conductors. Tratos PAS 5308-1 cables are available with both standard insulation thickness and enhanced insulation thickness with individual or collective screens to confine the electric field and to limit the external electrical influences. PAS 5308 Specification designate cables according to their construction, type 1 cables are unarmoured, type 2 cables have a single wire armour. Both types of cable have a PVC outer sheath, however recognising the contribution of cables to a fire hazard Tratos manufacture an equivalent range of cables with low smoke zero halogens (LSZH) sheath.

Electric cables used for the supply of electricity and for control and communication purposes, which are intended for use in buildings and other civil engineering construction works are covered by the Construction Products Regulation No. 305/2011 and subject to performance requirements on reaction to fire.

Tratos control and instrumentation cables are available as class Cca (BS EN 50575) as standard, higher classifications are available on request

The ranges of control and instrumentation cables have been rationalised to preclude certain cable types and conductor sizes in accordance with current industry practice.

STANDARDS

  • PAS 5038-1 – Design
  • BS EN 60288 class 1, class 2 or class 5 – Conductor
  • BS EN 50290-2-23 or BS EN 50290-2-23 – Insulation
  • BS EN 50290-2-22 or BS EN 50290-2-27 – Sheath

Where CPR applies

  • BS EN 50575
  • CPR BS EN 13501-6

Where CPR does not apply

  • IEC 60332-1 – Flame Retardant
  • IEC60332-3-22 – Flame retardant
  • IEC60754-1,2 – Halogen Free (on request)
  • IEC 61034-1,2 – Low Smoke (on request)

Contact us:

Tel: +44 20 3148 5178

e-mail: sales@tratosgroup.com

Please don’t hesitate to contact us if you need additional information about our products.

Application

Used for wiring control, protection, signalling, communication and data transmission circuits in industrial applications where individual or collective screening of the pairs by an earthed metallic layer to prevent cross talk and reduce external electrical influences is required. Type 1 control and instrumentation cables are unarmoured and therefore unsuitable for underground burial

CONSTRUCTION

  • Conductor: BS EN 60228 class 1, class 2 or class 5 plain annealed copper
  • Insulation: Grade L/MD thermoplastic polyethene (PE) to BS EN 50290-2-23 or Cross-linked PE (XLPE) to BS EN 50290-2-29
  • Individual pair screen (optional)
    • a) Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire
    • b) Polyester isolating tape(s) numbered for identification
  • Tape: Polyester binder tape
  • Collective screen (optional) - Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire
  • Outer sheath: Grade TM51 PVC to BS EN 50290-2-22 or on request halogen free flame retardant compound (LSZH) to BS EN 50290-2-27
  • Standard colour: Black (other colours available on request)

Standards

Technical Specifications

  • Control and Instrumentation
  • Rated voltage 150/250 
  • Maximum continuous conductor operating temperature for PE insulation 65 °C.
  • Maximum continuous conductor operating temperature for XLPE insulation 90 °C.
  • Minimum installation temperatures 0 °C.
  • Minimum operation temperature when installed  – 15 °C

Maximum DC Conductor resistance at 20 °C

  • 0.5 mm2 class 1 36.8 Ω/km
  • 1.0 mm2 class 1 18.4 Ω/km
  • 0.5 mm2 class 5 39.7 Ω/km
  • 1.5 mm2 class 2 12.3 Ω/km
  • 2.5 mm2 class 2 7.6 Ω/km

The maximum pair to pair capacitance unbalance shall be: 

  • For lengths of 250m, 250 pF at 1 kHz or 
  • For lengths other than 250 m (less than 100 m shall be considered as 100 m) 250 pF divided by the length gin metres of the cable under test.

Capacitance unbalance

The maximum pair to pair capacitance unbalance shall be:

  • a) For lengths of 250m, 250 pF at 1 kHz or
  • b) For lengths other than 250 m (less than 100 m shall be considered as 100 m) 250 pF divided by the length gin metres of the cable under test.

Minimum bending radius

Type 1 cables 6D

Contact us

Please, don’t hesitate to contact us for additional information on our company or our products.

Related Case Studies

Other News

Our website uses cookies and thereby collects information about your visit to improve our website (by analyzing), show you Social Media content and relevant advertisements. Please see our cookies page for further details or agree by clicking the 'Accept' button.

Cookie settings

Below you can choose which kind of cookies you allow on this website. Click on the "Save cookie settings" button to apply your choice.

FunctionalOur website uses functional cookies. These cookies are necessary to let our website work.

AnalyticalOur website uses analytical cookies to make it possible to analyze our website and optimize for the purpose of a.o. the usability.

Social mediaOur website places social media cookies to show you 3rd party content like YouTube and FaceBook. These cookies may track your personal data.

AdvertisingOur website places advertising cookies to show you 3rd party advertisements based on your interests. These cookies may track your personal data.

OtherOur website places 3rd party cookies from other 3rd party services which aren't Analytical, Social media or Advertising.