BS 5308-2 standard for Instrumentation cables, Specification for PVC insulated cables.

Overview

BS 5308 Part 2 specifies the requirements and dimensions for PVC-insulated instrumentation cables. These cables are designed primarily for the chemical and petrochemical industries and include options for screens, single-wire armour, or lead sheath with single-wire armour for additional protection. The cables are used to connect electrical instrument circuits and facilitate communications in demanding industrial environments. Although BS 5308 Part 2 has been withdrawn, manufacturers like Tratos can produce cables that adhere to the designs previously specified in the withdrawn standard.

Key Specifications

The cables are insulated with high-quality PVC material, ensuring durability and flexibility under various environmental conditions. They are suitable for operation at voltages up to 300 V r.m.s. core to earth and 500 V r.m.s. core to core. These cables are not intended for direct connection to low-impedance sources, such as public mains electricity supplies.

The conductors are made from plain annealed copper wire for optimal conductivity and mechanical performance. Two insulated conductors are twisted uniformly together to form a pair. For two-pair cables, if unscreened, the four cores are laid in quad formation around a central dummy. Unscreened pairs are colour-coded for identification, while screened pairs are identified using either coloured insulation or a numbered polyester film.

Protective armour options include a single layer of galvanised steel wire or a lead sheath with single-wire armour, providing enhanced mechanical strength and resistance to environmental factors. The outer sheath of the cables is made from a durable PVC material, which provides excellent resistance to moisture and chemicals.

Applications

These cables are primarily used in the chemical and petrochemical industries due to their robust insulation and protective design. While BS 5308 Part 1 focuses on polyethylene-insulated cables for the petroleum industry, BS 5308 Part 2 provides a complementary solution for environments requiring PVC insulation. These cables are not suitable for coal mining applications (Group I), but they may be used in Group II intrinsically safe systems, provided that relevant safety guidelines are followed.

Products

Contact us

Please, don’t hesitate to contact us for additional information on our company or our products.

Other News

Our website uses cookies and thereby collects information about your visit to improve our website (by analyzing), show you Social Media content and relevant advertisements. Please see our cookies page for further details or agree by clicking the 'Accept' button.

Cookie settings

Below you can choose which kind of cookies you allow on this website. Click on the "Save cookie settings" button to apply your choice.

FunctionalOur website uses functional cookies. These cookies are necessary to let our website work.

AnalyticalOur website uses analytical cookies to make it possible to analyze our website and optimize for the purpose of a.o. the usability.

Social mediaOur website places social media cookies to show you 3rd party content like YouTube and FaceBook. These cookies may track your personal data.

AdvertisingOur website places advertising cookies to show you 3rd party advertisements based on your interests. These cookies may track your personal data.

OtherOur website places 3rd party cookies from other 3rd party services which aren't Analytical, Social media or Advertising.